Fuelstretcher Technical Specification

General Features
  • Controls up to 4 boilers on the same header or only 2 boilers if Hi – Lo burners and controls are used.
  • Self-tuning – no programming – no user adjustment needed.
  • Manual override key for servicing and fault diagnosis.
  • Simple electrical installation by qualified electrician - entirely contained within boiler house – no outside sensors required.
  • No fuel or water pipe intrusion needed.
  • Provides optional control of HWS storage temperatures for Plant Room calorifiers.
  • Connects to burner circuit through main boiler panel or directly on to thermostats and/or Boiler Main Panel Control Circuits or BMS enabling relays.
  • Complies with all boiler manufacturers’ operating requirements.
  • 'Fails safe'.
  • LED Displays - Power - Boiler/Burner enable - Override ( Flashing )
Technical Specification
Power Supply (Must be permanent) 230VAC +15%/-18% 50/60HZ
Dedicated Full Disconnect 1 amp fused spur
Relay Outputs 4 x SPNC volts-free contacts
Relay Contact Rating 240VAC, 3.5A Inductive
Power Reserve (battery back-up) 6 hours minimum
Enclosure Rating IP65 (IEC529/DIN40050)
Max Ambient Temp 45 degrees C
Overall Dimensions 315W x 118D x 260H (excluding cables/glands)
Sensor Type Thermistor - resistance 30000 ohms@ 25°C
Sensor Cable Length 30 metres max